Installation
Procedure and Criteria for Masonry, Concrete and Steel Back-Up
- Select proper
anchor length based on wall make-up
- Drill approproate
hole at mortar joint (preferablt "T" location) using a rotary
hammer or hammer drill. Rotary only in soft material.
- Drill 1/2"
hole through outer wythe of material
- For solid
back-up, continue 1/2" hole drilling to a 2-2 1/2" depth minimum.
(or total depth 1/2" deeper than anchor length)
- For hollow
back-up, drill 3/8" diameter hole through the cavity face of the
inner wythe material
- Blow out excess drill fines
- Assemble threaded portion
of complete anchor assembly to the setting tool. Hex bolt on the setting
tool must be fully seated, thread anchor into setting tool until it
stops.
- Insert entire assembly into
drilled hole until it bottoms in the solid back-up or until the washer
contacts inner cavity face of hollow back-up.
- Rotate tool clockwise and
tighted back-up anchor 50-100 in-lb, remove setting tool.
- To remove setting tool,
loosen bolt head while holding setting tool firmly, spin off by hand.
- Slide socket drive tool
over hex segment of setting tool on to the hex nut of the anchor and
tighten to 50-100 in-lb.
- Remove socket and plug hole
|
|
|
|
|
|